The 100 Volt Line VIGIL2 Class D amplifiers are fully compliant
with BS5839 Part 8, EN60849 and EMC regulations. They are greater
than 80% efficient (compared to typical ‘A/B Class’
amplifiers of around 60%). They draw less current and, therefore,
do not generate unwanted heat, whic means smaller standby batteries
are required on a Watt to Watt basis.
VIGIL2 amplifiers are physically compatible with VIGIL A/B amplifiers
and each has two 500mV balanced inputs with selectable priority.
They have a sleep mode, reducing the standby requirements to typically
50mA per amplifier when operating on batteries. All VIGIL2 amplifiers
can achieve rated output power from a 22V battery supply.
The Power supply utilises Switch Mode Power techniques to improve
efficiency and, like the amplifiers, it is completely compatible
with previous VIGIL power supplies.
BV440M ~ Amplifier
The VIGIL2 BV440M is physically compatible
with the phased out A/B range, with an increased power output 440Watt.
CLASS D is 80% efficient. Switching output stages reduces unwanted
heat dissipation and power input, therefore smaller batteries will
be required for standby. Rated output power is attainable using
a 22V battery supply.
The amplifier
has a sleep mode, automatically reducing the standby requirements
to 70mA per amplifier when operating on batteries.
440Watt versions
can be paralleled to produce higher single output powers.
BV440M Amplifier
module may be mounted in one BVMF equipment frame with one switch
mode power supply / charger module.
The BV440M
Module is equipped with two 500mV balanced line inputs incorporating
a priority switching system. The priority is selected using a 4-way
DIL switch.
BVMF complete with BVSMP and one BV440. 2U in height. 19" rack
mountable.
The output stage is protected against overload
conditions (i.e. short circuits, etc) by means of sensing the current
and voltage and presenting this DC signal to a Voltage Controlled
Attenuator (VCA). Should the amplifier be subjected to an abnormal
load the input to the power amplifier is attenuated to a safe level
using the VCA. The amplifier’s output voltage is also sensed
and, should it exceed 100V, the VCA will be activated and again
will reduce the input signal, ensuring safe operation without creating
unnecessary distortion.
Over temperature protection is provided using a sensor attached
to the output stage heatsink. Should the temperature exceed 90ºC
the VCA attenuates the input signal to a safe level and illuminates
a warning LED. If the system is under surveillance it will cause
the surveillance detector to indicate a fault condition due to the
gain reduction. The inputs to the amplifier are presented on two
separate four-way plug-in terminal connectors; each connector provides
a balanced audio input, ground and access DC control input. The
output is presented on a three-way plug/screw termination connector
providing 50V or 100V output. The 24V DC input, together with the
necessary interface connections enabling several amplifiers to be
paralleled, are presented on a 6-way crimp connected plug and socket.
The front panel LED indicators include an output level status indicator
consisting of two LEDs indicating 10% and 100% maximum output level.
A ‘supply healthy’ indicator is also provided together
with ‘overload’, ‘over temperature’ and
‘active’ indicators.
BV220 ~ Amplifier
The VIGIL2 BV220 is physically compatible
with the phased out A/B range, with an increased power output of
220Watt.
CLASS D is 80% efficient. Switching output stages reduces unwanted
heat dissipation and power input, therefore smaller batteries will
be required for standby. Rated output power is attainable using
a 22V battery supply.
The amplifier
has a sleep mode, automatically reducing the standby requirements
to 50mA per amplifier when operating on batteries.
220Watt versions
can be paralleled to produce higher single output powers.
Up to three
BV220 Amplifier modules may be mounted in one BVMF equipment frame
or two amplifier modules and one switched mode power supply / charger
module.
The BV220
Module is equipped with two 500mV balanced line inputs incorporating
a priority switching system. The priority is selected using a 4-way
DIL switch.
BVMF complete with BVSMP and two BV220. 2U in height. 19" rack
mountable.
The output stage is protected against overload
conditions (i.e. short circuits, etc) by means of sensing the current
and voltage and presenting this DC signal to a Voltage Controlled
Attenuator (VCA). Should the amplifier be subjected to an abnormal
load the input to the power amplifier is attenuated to a safe level
using the VCA. The amplifier’s output voltage is also sensed
and, should it exceed 100V, the VCA will be activated and again
will reduce the input signal, ensuring safe operation without creating
unnecessary distortion.
Over temperature protection is provided using a sensor attached
to the output stage heatsink. Should the temperature exceed 90ºC
the VCA attenuates the input signal to a safe level and illuminates
a warning LED. If the system is under surveillance it will cause
the surveillance detector to indicate a fault condition due to the
gain reduction. The inputs to the amplifier are presented on two
separate four-way plug in terminal connectors; each connector provides
a balanced audio input, ground and access DC control input.
The output is presented on a three-way plug/screw termination connector
providing 50V or 100V output. The 24V DC input, together with the
necessary interface connections enabling several amplifiers to be
paralleled, are presented on a 6-way crimp connected plug and socket.
The front panel LED indicators include an output level status indicator
consisting of two LEDs indicating 10% and 100% maximum output level.
A ‘supply healthy’ indicator is also provided together
with ‘overload’, ‘over temperature’ and
‘active’ indicators.
BV120D ~ Amplifier
The VIGIL2 BV120D is a Dual 120Watt Amplifier
each with two 500 mV balanced inputs with selectable priority. It
is physically compatible with the phased out A/B range with only
a small wiring change if replacing an existing BV6060.
CLASS D is 80% efficient. Switching output stages reduces unwanted
heat dissipation and power input, therefore smaller batteries will
be required for standby. Rated output power obtainable using a 22V
battery supply.
Each Amplifier
has a sleep mode, automatically reducing the standby requirements
to 50mA per amplifier when operating on batteries.
Up to three
BV120D Amplifier modules may be mounted in one BVMF equipment frame
or two amplifier modules and one switched mode power supply / charger
module.
Each Amplifier
of the BV120D Module is equipped with two 500mV balanced line inputs
incorporating a priority switching system. The priority is selected
using a 4-way DIL switch.
BVMF complete with BVSMP and two BV120D. 2U in height. 19" rack
mountable.
The output stage is protected against overload
conditions (i.e. short circuits, etc) by means of sensing the current
and voltage and presenting this DC signal to a Voltage Controlled
Attenuator (VCA). Should the amplifier be subjected to an abnormal
load the input to the power amplifier is attenuated to a safe level
using the VCA. The amplifier’s output voltage is also sensed
and, should it exceed 100V, the VCA will be activated and again
will reduce the input signal, ensuring safe operation without creating
unnecessary distortion.
Over temperature protection is provided using a sensor attached
to the output stage heatsink. Should the temperature exceed 90ºC
the VCA attenuates the input signal to a safe level and illuminates
a warning LED. If the system is under surveillance it will cause
the surveillance detector to indicate a fault condition due to the
gain reduction. The inputs to the amplifier are presented on two
separate four-way plug in terminal connectors; each connector provides
a balanced audio input, ground and access DC control input. The
output is presented on a three-way plug/screw termination connector
providing 50V or 100V output. The 24V DC input is presented on a
two-way crimp connected plug and socket.
The front panel LED indicators include an output level status indicator
consisting of two LEDs indicating 10% and 100% maximum output level.
A ‘supply healthy’ indicator is also provided together
with ‘overload’, ‘over temperature’ and
‘active’ indicators.
BV050Q ~ Amplifier
The Vigil2 BV050Q contains four independent 50 Watt amplifiers,
each with one 500 mV balanced input for both emergency and non-emergency
inputs.
CLASS D is
80% efficient, switching output stages reduces unwanted heat and
power input, therefore smaller batteries will be required for standby.
Rated output power obtainable using a 22V battery supply.
Each Amplifier
has a sleep mode automatically reducing the standby requirements
to 50mA per amplifier when operating on batteries.
Up to three
BV050Q amplifier modules may be mounted in one BVMF equipment frame
or two amplifier modules and one switched mode power supply / charger
module.
Channel gain
may be individually set using the potentiometers on the board behind
the front panel.
BVMF complete with BVSMP and two BV050Q. 2U in height. 19" rack
mountable.
The output stage is protected against overload conditions (i.e.
short circuits) by means of sensing the current, voltage and presenting
this DC signal to a Voltage Controlled Attenuator (VCA). Should
the amplifier be subjected to an abnormal load the input to the
power amplifier is attenuated to a safe level using the VCA. The
amplifier’s output voltage is also sensed and, should, it
exceed 100V the VCA will be activated and again will reduce the
input signal ensuring safe operation without creating unnecessary
distortion.
Over temperature protection is provided using a sensor attached
to the output stage heatsink and should the temperature exceed 90ºC
the VCA attenuates the input signal to a safe level and illuminates
a warning LED. If the system is under surveillance it will cause
the surveillance detector to indicate a fault condition, due to
the gain reduction. The inputs to the amplifier are presented on
four separate four-way plug-in terminal connectors; each connector
provides balanced audio input and ground. The output is presented
on a 3-way plug/screw termination connector providing 50V or 100V
output. The 24V DC input is presented on a two-way crimp connected
plug and socket.
The front panel LED indicators include an output level status indicator
consisting of two LEDs indicating 10% and 100% maximum output level.
A ‘supply healthy’ indicator is also provided together
with ‘overload’, ‘over temperature’ and
‘active’ indicator.
BVSMP ~ Switch Mode Power Supply
BVSMP is physically compatible with our phased out A/B range. Switch
mode techniques improve efficiency, reducing unwanted heat dissipation
and weight.
Each unit
provides two independent power converters with current and over
voltage protection circuits, improved monitoring of charger and
all DC outputs to ensure reliability.
The power
supply provides two individually protected outputs at 24V to feed
either two BV220, two BV120D or one BV440M power output modules.
In the event of mains failure power is maintained using an external
standby battery which is continuously float charged by the charger
section of the PSU unit.
The unit has
built-in deep battery discharge cut off; this prevents total discharge
that can destroy the standby batteries in the event of AC power
failure for any long periods.
A third protected
output is provided to power a mixer or auxiliary circuits. All these
outputs, together with a fault volt free changeover contact, are
provided by a nine-way crimp connector plug and socket.
The charger
section is totally monitored and indicators for AC supply healthy,
fuse failure, charger fail, battery voltage high, and battery voltage
low are incorporated. Should any of the above fault conditions occur,
an internal relay releases providing a changeover contact, signalling
to the control system. The charger incorporated is of the constant
voltage type set for the recommended float charge.
Should the battery be below this float charge it will charge in
a constant current mode at the rate of three amps and progressively
reduces once the battery has achieved its nominal float level. Several
chargers may be paralleled when used for larger systems and must
be synchronised.
BVMF ~ Main Frame
Up to three BV220 or BV120D amplifier modules may be mounted in
one 2U equipment frame. Alternatively you can mount two amplifier
modules and one BVSM power supply/charger module.