Dimensions: 410mm (W) x 290mm (H) x 200mm (D) (08– 32
Way)
Dimensions: 410mm (W) x 455mm (H) x 200mm (D) (16 – 64
Way)
Dimensions: 410mm (W) x 777mm (H) x 200mm (D) (80 – 128
Way)
Bezel dimensions: 461mm (W) x 340mm (H) x 25mm (D) (08-32 way)
Bezel cut out dimensions: 420mm (W) x 300mm (H) (08-32 way)
Bezel dimensions: 461mm (W) x 506mm (H) x 25mm (D) (16 – 64
Way)
Bezel cut out dimensions: 420mm (W) x 465mm (H) (16 – 64
Way)
Remote Telephones:

Full or half duplex speech
Optional lockable door and/or beacon
Coloured red for emergency purposes
System healthy indicator
Push catch or slot lock
Contains both rugged handset and loudspeaker
Wall mountable – optional flush mountable bezel available
Dimensions: 130mm (W) x 350mm (H) x 100mm (D) – excludes
beacon
Bezel dimensions: 170mm (W) x 390mm (H) x 20mm (D)
Bezel cut out dimensions: 138mm (W) x 356mm (H)
System Requirements:
Enhanced fire rated four core cable with drain must be used, Baldwin Boxall recommends colour coded.
Up to 200m cable run between handsets and control panel as
standard
A ring circuit configuration must be used
A repeater unit must be used if distance between units exceeds
200m
Please contact our sales department for wiring methods

VIGIL FireCare utilises a ring circuit with typically sixteen handsets
on each ring. There can be up to 200m of cable between each. It
is possible to extend this distance by installing a repeater unit.
It is necessary for the first and last handsets to be no more than
200m from the Control Panel. By utilising this ring method it is
possible to save up to 75% on cabling costs when compared with typical
star circuit systems. The intelligence of the system ensures that
if the circuit were to be broken at any point on the loop, the system
will still operate without loss of communication.

|