Master Control Panel:
Features as standard
VIGIL CommuniCare Master Control Panel apart from:
Activated
via the building's fire detection System.
Emergency
overide and test contact via break glass unit (break glass
unit not supplied).
Dimensions: W 410mm H 290mm D 200mm (08 - 32 Way)
Dimensions: W 410mm H 455mm D 200mm (16 - 64 Way)
Remote
Unit:
Half duplex speech.
Green
finish.
All
text is tactile, in Braille and is luminescent.
In
built induction loop.
System
in standby/healthy, activated and 'occupied' indicator.
Volt
free contact, active when occupied. To operate over-door
lamps, silence speaker/sounder etc.
Reset
facility.
Wall
mountable - flush or surface mount.
Self-powered
from ring circuit.
Up
to 16 remote units per loop.
Dimensions
- Flush Mount: 178mm(W) x 440mm(H) x 65mm(D).
Dimensions
- Surface Mount: 180mm(W) x 440mm(H) x 64mm(D).
Flush
mount cut out dimensions: 133mm(W) x 235mm.
Knockouts,
20mm and 25mm diameter in sides of back box.
Weight
1kg.
System
Requirements :
Enhanced fire rated four core cable with drain must be used, Baldwin Boxall recommends colour coded.
Up
to 200m cable run between remotes and control panel as standard.
A ring
circuit configuration must be used, please contact our sales
department for wiring methods.
A repeater
unit must be used if distance between units exceeds 200m.
Up
to 16 remote units per loop.
The
ring configuration allows for auto-commissioning; as the
system 'self-learns' and numbers all remote units.
Please note the unit is not VOX
operated. |