Fully BS5839
part 9 compliant, when installed according to the standard
Dimensions:
410mm (W) x 455mm (H) x 200mm (D) (16-64 way)
Dimensions:
410mm (W) x 777mm (H) x 200mm (D) (80-128 way)
Bezel dimensions:
461mm (W) x 506mm (H) x 25mm (D) (16-64 way)
Bezel cut
out dimensions: 420mm (W) x 465mm (H) (16-64 way)
Knockouts,
20mm diameter in top and top/rear
Distinguishing 'Blue'
name panel
Weight (including
battery) 26kg
Remote Unit:
 Half duplex
speech
Red
or stainless steel finish
System
healthy indicator
Volt
free contact, active when occupied. To operate over-door
lamps, silence speaker/sounder etc.
Call
switches
 Wall
mountable - optional flush mountable bezel available
Self-powered
from ring circuit
Typically
20-30 remote units per loop
Dimensions:
134mm (W) x 134mm (H) x 46mm (D)
Bezel
dimensions: 154mm (W) x 154mm (H) x 10mm radius
Bezel
cut out dimensions: 136mm (W) x 136mm (H) x 10mm radius
Knockouts,
20mm and 25mm diameter in sides of back box
Weight
1kg
System Requirements:
Wiring between
Master Console and Secondary Master Consoles requires two (x2)
4-core cables between each Console
Enhanced fire rated four core cable with drain must be used, Baldwin Boxall recommends colour coded.
Up
to 200m cable run between handsets and control panel as standard
A
ring circuit configuration must be used to wire the remotes
A
repeater unit must be used if distance between units exceeds
200m
Please
contact our sales department for wiring methods
VIGIL AssureCare
has simplified wiring needs. Remote units situated in strategic
positions within a building are wired back on a loop to a Secondary
or Master Console. The only limit on the number of remote units
is voltage loss, 20-30 units is typical before such loss is critical
to system performance. The wiring between the Master Console
and Secondary Master Consoles is also simplified; you will only
require two (x2) 4-core cables between each Console.
The cable(s)
required for the loops are a 4-core with screen arranged as a
ring circuit, and there can be typically up to 30 remotes on each
loop. We normally recommend that you can have up to 200 metres
of cable between each remote.

|